Test and Tag Interval Table
This table must be read in conjunction with Australian Standard 3760.2003. Intervals between testing must not exceed the following
|
Type of environment and/or equipment
(a) |
Interval between inspection and tests |
||||||||||||
|
Class of equipment |
Residual Current Devices (RCDs) |
Cord extension set and Power boards
(h) |
|||||||||||
|
Class 1
Protectively earthed
(b) |
Class 2
Double insulated
(c) |
|
|||||||||||
|
|
|
|
|
|
|
|
|
||||||
|
Construction work |
Monthly |
Monthly |
Monthly |
Monthly |
Monthly |
Monthly |
Monthly |
||||||
|
1. Factories, workshops, places of repair, manufacturing, assembly, maintenance or fabrication |
6 months |
12 months |
Daily or before every use, whichever is longer |
6 months |
12 months |
12 months |
6 months |
||||||
|
2. Environment where the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment |
12 months |
12 months |
3 months |
6 months |
12 months |
12 months |
12 months |
||||||
|
3. Environment where the equipment or supply is NOT subject to flexing in normal use and is NOT open to abuse and is NOT in a hostile environment |
5 years |
5 years |
3 months |
6 months |
2 years |
2 years |
5 years |
||||||
|
4. Residential type areas: hotels, residential institutions, motels, boarding, houses, halls, hostels, accommodation houses and the like |
2 years |
2 years |
6 months |
6 months |
2 years |
2 years |
2 years |
||||||
|
5. Equipment used for commercial cleaning |
6 months |
12 months |
3 months |
N/A |
12 months |
N/A |
12 months |
||||||
|
6. Hire Equipment:a) Inspection |
Prior to hire |
Including push button test by hirer prior to hire |
N/A |
N/A |
Prior to hire |
||||||||
|
b) Test and tag |
3 months |
N/A |
3 months |
12 months |
3 months |
||||||||
|
7. Repaired or services equipment |
After repair or service, which could have affected electrical safety, or on reintroduction to service. |
||||||||||||